Control Panel Description and Installation
150964 4-25
4.15.6 Zone Response (Debounce) Speed
Through programming, you select the zone response speed for the type of hardware you are
installing. The chart below shows the response (debounce) speeds available. The very fast rate
of 10 milliseconds (needed for devices such as audio glass break detectors) is available only
for internal or 4825 type zones. See Section 6 of this manual for details about how to make
selections for zone options.
Note: In the Response Speed column above, the range of numbers in parentheses shows the duration (millisec-
onds or seconds) that the zone response speed represents. The larger number is the minimum duration that
the zone must remain in a changed state in order for the change to always be recognized by the system. The
smaller number is the maximum duration that the zone can be in a changed state in order to
not
be recog-
nized by the system.
Example: 10 msec Response Speed
Response Speed Available with:
Internal
(Built into
4821/4820
board)
4825
(Hardwire
Expansion
Zones)
4815
(Serial
Expansion
Zones)
4860C & 4421
(Touchpad
Zones)
10 milliseconds
(9-18 msec)
Yes Yes No No
100 milliseconds
(55 - 100 msec)
Yes Yes No Yes
250 milliseconds
(220 - 330 msec)
No No Yes No
1 second
(0.5 - 1.0 seconds)
Yes Yes Yes Yes
10 seconds
(5 - 10 seconds)
Do not use with smoke
verification zones. See
Section 6.3.2.3.
Yes Yes Yes Yes
If the zone change of state lasts: The zone state change is:
longer than 18 msec ALWAYS recognized
shorter than 9 msec NEVER recognized
between 9-18 msec might be recognized, but NOT GUARANTEED