Model 4821/4820 Control/Communicator Installation Manual
6-28 150966
Events to Report For the list of events below, select Yes, No, or Must.
Selecting Must forces the event to be reported to this account. The dialer will con-
tinue attempting to report Must events until all attempts have been made for events
selected as Yes or Must. If the event was not successful, it will remain in the report
buffer until a new event needs to be reported. The dialer will then attempt to report
the old Must event.
Selecting Yes allows the event to be reported to this account. If the account has the
highest priority, the dialer will attempt to report the event to that account first. If
the report was successful, the event will not be reported to any other Yes accounts.
Selecting No means the event will not be reported to this account.
No (for all
events)
Open-Close Send normal open and close reports to this account number.
Alarm Report alarms to this account number.
Trouble Report troubles and trouble restores to this account number.
Bypass Report bypassed and reinstated (unbypassed) zones to this
account number.
Alarm Restore Report alarm restores to this account number.
Alarm Reset Report open and reset alarms to this account number.
Door Access Report door access events to this account number.
Test Report test signals to this account number.
Date/Time Event Send the system date and time with events that are reported.
Used when the reporting device is 4824 serial or parallel
port.
Exception OPCL
(Exception open-
close)
Report exceptional open and close events to this account
number.
An exception open/close event occurs when an area is open
or closed outside of the normal open/close time schedules.
Trouble OPCL
(Trouble open-
close)
Report open or close troubles to this account, indicating that
an area within the partition has failed to arm or disarm dur-
ing a specified time schedule.
System Report all system troubles (including low battery, low AC
and phone line troubles) to this account number.
Door Access De-
nied
Report door access denied events.
Door Exit Report all door exit events.
Door Left Open Report doors that remain open after the door held open timer
expires.
Table 6-9: Reporting Accounts Options and Description
Option Description Default