Model 5700 Installation and Operation Manual
4-22 151295
4.7.4 Dry Contact Wiring
The 8 input circuits on the 5880 board are for monitoring switch inputs-any type of switch
supported by the control panel can be used with the 5880. For example, you can use a 5880 to
monitor pull stations, water flow, tamper, reset, or silence switches.
Wire dry contacts as shown in Figure 4-22. Notice grouping of terminals; power terminals are
shared by two inputs.
Figure 4-22 Dry Contact Wiring
Model 7628
Supervised
4.7kΩ EOL