SILENT KNIGHT 5700 Spécifications Page 101

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 186
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 100
Programming
151295 7-9
Example or Zone Mapping:
Suppose you want to program Zone 1 so that:
Any alarm (detector, water flow or manual pull) would activate Output Group 1 using the
ANSI cadence pattern.
Manual pull alarm would activate Output Group 3 using constant output.
Troubles would activate Output Group 2 using the zone-coded cadence pattern.
To accomplish this you need to access the screen for each event and then select your output
groups. Figure 7-4 shows how you would program this application.
Figure 7-4 Zone Mapping Example
Vue de la page 100
1 2 ... 96 97 98 99 100 101 102 103 104 105 106 ... 185 186

Commentaires sur ces manuels

Pas de commentaire