Programming
151295 7-33
7.6.3.2 System Alarm Cadence
Fire drill and system auxiliary alarm events can have special cadence patterns to distinguish
them from other types of alarms. See Section 7.3.1.4 for available cadence patterns.
A typical use of the System Aux1 and Aux2 patterns is to distinguish fire emergencies from
other types of emergencies. For example, you could use one pattern for fire drills and a
different pattern for severe weather conditions. The System Aux1 and Aux2 alarms would be
triggered by a system-wide switch.
To access the screen for selecting output groups and cadence patterns for system trouble
events:
1. Press or to display the main menu.
2. Enter the installer code if requested.
3. Select for Program Menu.
Display reads: Initializing
Please wait . . .
4. From the Program Menu, select for System Options.
5. From the System Options Menu, select for Sys. Event Outputs.
6. Press for System Alarm Cadence.
A screen similar to the one in Figure 7-15 will display. Select a cadence pattern for these
special events if required for your application.
Figure 7-15 Special Cadence Patterns for Fire Drill and Auxiliary Alarm Events
7
5
3
2