Vue de la page 160
151274-L8
A-1
Appendix A
Compatible Devices
A.1 Notification Appliances
For proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on each loop.
All supervised notification appliances used with the control panel must be polarized.
Note:
Not all devices can use the Sync feature, be sure to check Table 0-1 to ensure the device you have chosen will work with
this feature. This control is UL listed for panel wide Synchronization.
Table below lists notification appliances compatible with the fire alarm control panel. Appliances which can be
synchronized indicate the type of SYNC available in the columns marked Audio and Visual.
Table A-1: Compatible Notification Appliances
Manufacturer Model Audio Visual Type
AMSECO
SH24W-153075
xx
Horn/Strobe
SAD24-153075
x
Strobe
SAD24-75110
x
Strobe
SL24W-75110
x
Strobe
SL24C-3075110
x
Strobe
SLB24-75
x
Strobe
RSD24-153075
x
Strobe
RSD24-75110
x
Strobe
SH24W-75110
xx
Horn/Strobe
SH24W-3075110
xx
Horn/Strobe
SHB24-75
xx
Horn/Strobe
SCM24W-153075
x
Chimes/Strobe
SCM24W-75110
x
Chimes/Strobe
SCM24C-3075110
x
Chimes/Strobe
SCM24C-177
x
Chimes/Strobe
H24W
x
Horn
H24R
x
Horn